Cable Structure | |
---|---|
Generally Conforms to, IS 694, BS 6004, IEC 60227, DIN VDE 0281-3, IS 8130 & IS 5831C | |
Copper | EC flexible copper generally conforms to IEC 60228, IS 1830 |
Insulation | FR+HR/FRLS-H/ZHFR Insulation compound with a high insulation resistance value. (-15° C to +70° C / +90° C/ +105° C) |
Colour | Blue, Red, Brown, Grey, Orange, White, Green, Yellow. |
* Any other Color on specific request can also be supplied |
Cable Structure | ||
---|---|---|
FR PVC Insulated cable | FRLS PVC Insulated cables | ZHFR Cable |
High flame retardant properties | Better Flame retardant property | Zero Halogen acid gas evolution |
Excellent resistant to moisture, abrasion, grace, oil | Less Halogen acid gas evolution | Non corrosive and non toxic insulation |
Longer flex life | Resistant to moisture, abrasion, grace, oil | High temperature resistant insulation |
Excellent mechanical & electrical properties | Excellent mechanical & electrical properties | Resistance to tarnishing of copper |
Tested by SGS, EIL, RITES, NCP, INTERTEK | ||
Steam and boiling Water Resistant |
Application | |
---|---|
Fixed installation in conduits and under plaster. | |
For appliance wiring and distribution station like Commercial Complexes, Buildings, Factories, Commercial construction, Hospitals and Residencies Apartments etc. | |
Standard length cable packing: Coils 90m & 180m in carton boxes, reels. |
FR/FRLS/ZHFR UP TO 1100 V. | ||||||
---|---|---|---|---|---|---|
Nominal cross section area of conductor | Number/Nominal dia of strands | Nominal insulation thickness | Max. Overall Diameter | Max. conductor resistance at 20⁰C | Current rating | |
Casing | Concealed | |||||
Sq. mm. | mm | mm | mm | Ω/km | Amps | Amps |
1.0 | 14/0.30 * | 0.7 | 2.8 | 18.1 | 14 | 13 |
1.5 | 22/0.30 * | 0.7 | 3.0 | 12.1 | 18 | 16 |
2.5 | 36/0.30 * | 0.8 | 3.7 | 7.41 | 24 | 20 |
4.0 | 56/0.30 ** | 0.8 | 4.2 | 4.95 | 32 | 26 |
6.0 | 84/0.30 ** | 0.8 | 4.8 | 3.30 | 42 | 35 |
- * class 2 Stranded conductor
- ** Class 5 Flexible conductor
F R Properties | ||||||
---|---|---|---|---|---|---|
Test | Specified | Specified Values | ||||
Limited Oxygen Index Test | IS 10810-58 | > 29% | ||||
Limited Temperature Index Test | IS 10810-64 | > 250* |
F R L S / ZHFR Properties | ||||||
---|---|---|---|---|---|---|
Test | Specified | Specified Values | ||||
Limited Oxygen Index Test | ASTM-D 2863 | > 32% | ||||
Limited Temperature Index Test | ASTM-D 2863 | > 250 * | ||||
Smoke Density (Light Absorption) | IASTD-D 2843 | < 50% | ||||
Acid Gas Generation | IEC- 60754-1 | < 18% |