whatsapp
  • Call us

    +91 95865 68656

  • Send us mail

    info@voltsonindia.com

Cable Structure
Copper Multiple-wire, round copper conductor class 2, DIN VDE 0281, IEC 60228
Insulation PVC insulation compound TI-1
Colour Green/Yellow, Blue, Black, Brown, Gray, Orange, Pink, Red, Violet, White, Green, Yellow or other colours
Flame propagation Flame retardant test as per IEC 60332-1
Technical Data
Operating Temperature -20°C max. +80°C
Nominal Voltage HO5V-R : 300/500 V
HO7V-R : 450/750 V
Test Voltage HO5V-R : 2000V
HO7V-R : 2500V
Insulation resistance Min. 10 MΩ x km
Min. bending radius 4 x cable diameter
Application
Fixed installation in conduits and under plaster, for appliance wiring and distribution stations
Standard length cable packing: Coils 100 and 200 , in carbon boxes, reels
Features
Good application of insulation Excellent mechanical & electrical properties
Special heat resistant insulation Harmonized acc. To European standards
High current carrying capacity Steam and boiling water resistant
Excellent resistant to moisture, abrasion, grace and oil. Tested by SGS, EIL, RITES, NCP, INTERTEK
Cable Structure
Copper Multiple-wire, round copper conductor class 2, DIN VDE 0281, IEC 60228
Insulation Heat - resistant PVC core insulation
Colour Green/Yellow, Blue, Black, Brown, Gray, Orange, Pink, Red, Violet, White, Green, Yellow or other colours
Flame propagation Flame retardant test as per IEC 60332-1
Technical Data
Operating Temperature -20°C max. +80°C
Nominal Voltage HO5V2-R : 300/500 V
HO7V2-R: 450/750 V
Test Voltage HO5V2-R : 2000V
HO7V2-R : 2500V
Insulation resistance Min. 20 MΩ x km
Min. bending radius 4 x cable diameter
Application
Fixed installation in conduits and under plaster, for appliance wiring and distribution stations
Standard length cable packing: Coils 100 and 200 , in carbon boxes, reels
Features
Good application of insulation Excellent mechanical & electrical properties
Special heat resistant insulation Harmonized acc. To European standards
High current carrying capacity Steam and boiling water resistant
Excellent resistant to moisture, abrasion, grace and oil. Tested by SGS, EIL, RITES, NCP, INTERTEK
Cable Design
A Submersible Pump Cable is a specialized product to be used for submersible pump in a deep well. The area of installation is physically restrictive, and the environment is very hostile. Voltson is designed and manufacured keeping in mind these factors to achieve the highest possible degree of reliability.
HO5V-U 300/500 V , HO5V2-U 300/500 V
Nominal cross sectional area of conductor Nominal insulation thickness Mean overall diameter Max conductor resistance at 20°C Min insulation resistance at 70°C
Lower limit Upper limit
Sq. mm. mm mm mm Ω/km MΩ/km
0.5 0.6 2.0 2.4 36.0 0.014
0.75 0.6 2.2 2.6 24.5 0.012
1.0 0.6 2.3 2.8 18.1 0.011
HO5V-R (300/500 V), HO5V2-R (300/500 V)
Nominal cross sectional area of conductor Nominal insulation thickness Mean overall diameter Max conductor resistance at 20°C Min insulation resistance at 70°C
Lower limit Upper limit
Sq. mm. mm mm mm Ω/km MΩ/km
1.50 0.7 2.7 3.3 12.1 0.010
2.50 0.8 3.3 4.0 7.41 0.0099
4.00 0.8 3.8 4.6 4.61 0.0082
6.00 0.8 4.3 5.2 3.08 0.0070
10.0 1.0 5.6 6.7 1.83 0.0067
16.0 1.0 6.4 7.8 1.15 0.0056
25.0 1.2 8.1 9.7 0.727 0.0053
35.0 1.2 9.0 10.9 0.524 0.0046
50.0 1.4 10.6 12.8 0.387 0.0046
70.0 1.4 12.1 14.6 0.268 0.0040
95.0 1.6 14.1 17.1 0.193 0.0039
120 1.6 15.6 18.8 0.153 0.0035
150 1.8 17.3 20.9 0.124 0.0035
185 2.0 19.3 23.3 0.0991 0.0035
240 2.2 22.0 26.6 0.0754 0.0034
300 2.4 24.5 29.6 0.0601 0.0033
400 2.6 27.5 33.2 0.047 0.0031
500 2.8 30.5 26.9 2.0366 0.0030
630 2.8 34 41.1 0.0283 0.0027
  • All are class 2 flexible conductor
  • Insulation grade is TI1