whatsapp
  • Call us

    +91 95865 68656

  • Send us mail

    info@voltsonindia.com

Cable Structure
Generally Conforms to, BS EN 50525, CENELEC HD 22.1.S2, DIN VDE 0282 PART 810, IEC 245, CEI 20-19 & BS 6007, BS 6899
Copper EC flexible copper generally conforms to IEC 60228, DIN VDE 0295,IS 8131
Insulation Special Rubber EPR, EPDM core.
Outer Sheath Special Rubber : Black, Blue
* Any color can be supplied as per the requirement and wish of the buyer.
Technical Data
Operating Temperature -40°c to max.+90°C
Nominal Voltage 450/750 V
Test Voltage 2.5 KV
Min. Bending Radius 6 x Cable diameter
Flame Propagation Flame retardant test as per IEC 60332-1
Application
Submersible Pump Cables are used as supply and control cables.
These cables are used in submersible pumps, underwater lighting, and floating switches etc.
Up to the depth of 500 m and water temperature up to +75°C .
These cables are ideal for outer installations in dry, moist and wet environments but however not suitable for explosive areas.
Cables are designed and manufactured to achieve the highest possible degree of reliability.
Standard length cable packing: Coils 100, 200, 300 and 500, 1000m . in wooden reels
Features
Meets the requirement of CENELEC HD 22.1.S2, DIN VDE 0282 PART 810, UL-83 IEC 245, CEI 20-19 & BS 6007, BS 6899 Excellent Impact Resistant
Temperature range -40° to +90° Excellent Weather Resistant
Designed for heavy duty use Performs & Looks like Vulcanize Rubber
Cut, tear & abrasion resistant Excellent Electrical Properties
Exceptional long term performance. Approved by GWSSB, GWRDC, TWAD, PHED, PSTC, ONGC
Excellent resistant to oils, chemicals, ozone & solvents Tested by INTERTEK,SGS, EIL, RITES, NPC
The area of installation is physically restrictive, and the environment is very hostile.
Cable Design
A Submersible Pump Cable is a specialized product to be used for submersible pump in a deep well. The area of installation is physically restrictive, and the environment is very hostile. Voltson is designed and manufacured keeping in mind these factors to achieve the highest possible degree of reliability.
Core Color : Core Indentification
Color Coding AS Per BS EN 50525 & IEC 60227 AS Per IS 694
3 Core Black, Light Blue and Brown Red, Yellow and Blue
4 Core Black, Light Blue, Brown, Yellow with Green Line / Green with Yellow Line Red, Yellow, Blue Green/Black
H07RN-F - 3 core
Number of cores & cross sectional area of conductor Nominal insulation thickness Nominal thickness of sheath Mean overall diameter Max conductor resistance at 20°C
Lower lmit Outer limit
nxsqmm mm mm mm mm Ω/km
1.5 0.8 1.6 9.2 11.9 13.3
2.5 0.9 1.8 10.9 14.0 7.98
>4.0 1.0 1.9 12.7 16.2 4.95
6.0 1.0 2.1 14.1 18.0 3.30
10 1.2 3.3 19.1 24.2 1.91
16 1.2 3.5 21.8 27.6 1.21
25 1.4 3.8 26.1 33.0 0.780
35 1.4 4.1 29.3 37.1 0.554
50 1.6 4.5 34.1 42.9 0.386
70 1.6 4.8 38.4 48.3 0.272
95 1.8 5.3 43.3 54.0 0.206
H07RN-F - 4 core
Number of cores & cross sectional area of conductor Nominal insulation thickness Nominal thickness of sheath Mean overall diameter Max conductor resistance at 20°C
Lower lmit Outer limit
nxsqmm mm mm mm mm Ω/km
1.5 0.8 1.7 10.2 13.1 13.3
2.5 0.9 1.9 12.1 15.5 7.98
4.0 1.0 2.0 14.0 17.9 4.95
6.0 1.0 2.3 15.7 20 3.30
10 1.2 3.4 20.9 26.5 1.91
16 1.2 3.6 23.8 30.1 1.21
25 1.4 4.1 28.9 36.6 0.780
35 1.4 4.4 32.5 41.1 0.554
50 1.6 4.8 37.7 47.5 0.386
70 1.6 5.2 42.7 54 0.272
95 1.8 5.9 48.4 61 0.206
  • The number of wires is approximate and wire diameter is nominal; they shall be such as to satisfy the requirements of conductor resistance as per Class 5 of IEC 60228 / DIN VDE 0295 / IS 8130 / BS 6360
  • In view of continuous improvements in our design and process, specifications given here in are subject to change without notice.